HART® Temperature Transmitter TxIsoBlock-HRT

Home » Products » Sensing, Conditioning & Transmitters » Temperature Transmitters » Hart® Temperature Transmitter Txisoblock-hrt

01 - ISO 900102 - Reach Compliance03 - RoHS06 - CE07 - UKCA11 - Ensured Accuracy16 - SigNow18 - HART

TxIsoBlock-HRT


HART® Temperature Transmitter

Temperature transmitter TxIsoBlock-HRT combines the proven quality of HART® certification with the robustness of NOVUS devices. The transmitter is compatible with HART® certified devices and it has electrical isolation between input and output, supporting voltage surges up to 1.5 kVrms. Its great differential is the total configuration through the two 4-20 mA current loop wires, which means more features for device configuration and monitoring.

 

By using a worldwide known protocol with more than 40 million field instruments supporting HART® technology, NOVUS's temperature transmitter TxIsoBlock-HRT enables the use of standard HART® configuration and supervision software that provides flexibility to users.



Still, unsure? Ask an expert! Make a Suggestion See all models

- Input Type: J, K, T, N, R, S, B, E, Pt100, Pt1000, NTC and 0-50 mV
- Accuracy Typical:
  Pt1000 / mV: 0.07 % span
  Pt100: 0.08 % span
  T/C: 0.07 % span ±1 °C (1.8 °F)
  NTC: 0.2 °C (0.36 °F)

- Maximum:
  Pt1000 / mV: 0.15 % span
  Pt100: 0.15 % span
  T/C: 0.15 % span ±1 °C (1.8 °F)
  NTC: 0.45 °C (0.81 °F)"

- Output Type: 4-20 mA

- Output Resolution: 0.25 µA

- Thermal Drift: < 0.05 % / 25 °C (77 °F)

- Isolation Input-Output: 1.5 kVrms

- Electric Protection: Reverse Polarity

- HART® Version: HART V7, compatible with HART V5

- Configuration Interface: Through TxConfig-HRT adapter or HART®
certified HandHeld

- Configuration Software: TxConfig II

- Approvals / Regulations: CE, NAMUR NE43, RoHS, Reach, HART®

- Electromagnetic Compatibility
  CISPR 11
  EN 61000-4-2
  EN 61000-4-3
  EN 61000-4-4
  EN 61000-4-5
  EN 61000-4-6
  EN 61000-4-8

- Operating Conditions: -40 to 85 °C (-40 to 185 °F) | 0 to 90% RH

- Power Supply: 4-20 mA Loop Powered (8.5 - 36 Vdc)

- Enclosure: PA66

- Format / Mounting: Head Mount

Related News

  • 12/5/2019

    HART technology is simpler than it seems, and NOVUS can show you that!

    Now TxIsoRail-HRT and TxIsoBlock-HRT temperature transmitters can be purchased in a starter kit that put consumers closer to HART Technology.

  • 8/6/2019

    NOVUS launches temperature transmitters with HART Protocol

    TxIsoRail-HRT and TxIsoBlock-HRT bring the robustness of NOVUS devices combined with HART® protocol certification, recognized worldwide as an industry communication standard for smart field devices.

  • 3/26/2019

    Article: The HART Communication Protocol

    Communication with machinery and control and measuring instruments is the basis of industrial automation. The oldest communication technique implemented is a current loop with a normal range of 4 mA to 20 mA. By employing a transmitter, a receiver and a power supply, it is possible to transmit process variable data. However, the single loop allows only one-way communication from a sensor to an actuator. Developed in the mid-1980s, the HART protocol allows two-way communication of additional information

Share: