Ethernet I/O Module DigiRail Connect

Home » Products » Data Acquisition & Communication » I/o Modules » Ethernet I/o Module Digirail Connect

01 - ISO 900102 - Reach Compliance03 - RoHS06 - CE07 - UKCA15 - NXperience

DigiRail Connect


Ethernet I/O Module

DigiRail Connect is a versatile I/O module to be used as an extension of any brand automation system. Its rich mixed inputs and outputs offer industrial standard analog and digital signaling. The available DigiRail Connect options ensure the choice of suitable configuration for the customer application.

 

Bringing the Industry 4.0 to the rail level, the connectivity of DigiRail connect allows it to be used as slave Modbus RTU device in RS485 networks or as a server Modbus TCP device under Ethernet network.

 

Specially designed for harsh environments, DigiRail Connect complies with the main EMC and EMI standards, providing robustness and reliability for industrial applications.



Still, unsure? Ask an expert! Make a Suggestion See all models

- Inputs:
  RAMIX: 4 digital and 2 analog (isolated)
  DMIX: 8 digital

 

- Outputs:
  RAMIX: 3 digital or 2 relay and 2 analog (isolated)
  DMIX: 4 relays or 8 digital

 

- Analog signals:
  Thermocouples J, K, T, N, E, R, S and B
  Pt100, Pt1000, NTC,
  0-60 mV, 0-5 V, 0-10 V, 0-20 mA, 4-20 mA

 

- Analog input impedance:
  0-60 mV, Pt100, Pt1000, NTC and thermocouples: >10 MΩ
  0-5 V, 0-10 V: >1 MΩ
  4-20 mA: 15 Ω + (1 V @ 20 mA)

 

- Digital Input characteristics:
  Logical level "0": < 0.5 V
  Logical level "1": > 3 V
  Maximum voltage: 30 V
  Input impedance:270 kΩ
  Input current: @ 30 Vdc (typical) 0.15 mA
  Maximum frequency (square wave):
  Dry contact: 10 Hz
  PNP: 250 Hz
  NPN: 250 Hz

 

- Digital Output characteristics:
  Maximum load current: 200 mA
  Short circuit current: 70 mA
  Maximum switching voltage: 30 Vdc
  Minimum switching voltage: 6 Vdc

 

- Relay Output characteristics:
  Type: SPST-NO and SPDT
  Maximum load current: 3 A (SPST) / 6 A (SPDT)
  Switching voltage: 250 Vac
  Suitable for resistive loads

 

- Analog Output characteristics:
  Signal types: 0-20 mA, 4-20 mA, 0-10 V
  Maximum load: 0-20 / 4-20 mA: ≤ 500 Ω
  0-10 V: ≥ 2000 Ω

 

- Analog Channel resolution:
  Analog inputs: 16 bits (65000 levels)
  Analog outputs: 12 bits

 

- Communication interface:
  USB
  Ethernet: 10/100 Mb/s, IEEE standard 802.3u
  RS485

 

- Software:
  NXperience (via USB)

 

- Power Supply:
  Voltage: 10 Vdc to 36 Vdc
  Maximum Consumption: 5 W
  Typical Consumption: 20 mA

 

- Operating conditions:
  Temperature: -20 to 60°C ( -4 to 140°F)
  Humidity: 5 to 95% RH, non-condensing

 

- Enclosure: ABS+PC

 

 

 

 

 

 

 

 

 

 

 

 


        